Installation and Operating Instruction for B.E.G.-Occupancy detectors PD4-Master-TRIO-DALI-SM/-FC
A Light sensor 1 | B Light sensor 2
1 LED red OFF function
2 LED green too bright/too dark CDS 1
3 LED white semi-automatic DA 1/2
4 LED white semi-automatic DA 3
5 LED green too bright/too dark CDS 2
6 LED red motion indicator/walking test
2a.
Installation of the LUXOMAT
®
PD4-M-TRIO-DALI-SM
2b.
Installation of the
LUXOMAT
®
PD4-M-TRIO-DALI-FC
3. Hardware configuration
Position of light sensors and LEDs
LUXOMAT
®
PD4-M-TRIO-DALI
1. Mounting preparations
Work on the 230 V mains supply
may only be carried out by quali-
fied professionals or by instructed
persons under the direction and
supervision of qualified skilled elec-
trical personnel in accordance with
electrotechnical regulations.
Disconnect supply before installing!
When in Master/Slave mode of
operation, the Master-appliance
must always be installed at the
location where there is least
daylight.
Option:
Wall bracket for remote
control
IR-PD4-TRIO-DALI
A4 5 1 3 2 6
B
GB
6. Putting into operation / Settings
Self test cycle
After an initial 60-second self-test cycle, the LUXOMAT
®
PD4-M-TRIO-DALI
is ready for operation.
Potentiometer 3: Follow-up time for light control
The time can be set infinitely variably at between
1 and 60 minutes. The time-setting is valid for all three chan-
nels of the PD4-M-TRIO-DALI.
Symbol TEST: Test mode (Every movement switches on the
light for a period of 2 second, switching it off for a period of
2 seconds after that regardless of the level of brightness.)
Potentiometer 2: Twilight-switch for light control
The switch-on value for the light can be set at between 40
and 1200 Lux. Using the rotary control, the luminance set
points can be set as desired.
Symbol
: Night-time operation
Symbol
: Daytime/Night-time operation
Potentiometer 1: Orientation lighting
This rotary controller serves to determine the working time of
the orientation lighting (fixed to 20 %).
“ON” for permanent orientation lighting.
“OFF” for deactiviation of orientation lighting.
45
30
15
5
1
TEST
60
1200
600
200
40
60
5
15
30
45
ON
OFF
80 - 90 mm
100 mm
C
DA 1/2 ON/OFF
max
50
Lux
1500
Lux
ON
OFF
Settings by remote control


60


10
to
or
to
60
min
1
min
to
or
Fully /semi automatic mode
(only
DA 1/2
)
=> see page 2, point 7
LED display ON/OFF
Resetting when
open: All values
which have been
programmed
using the remote
control are de-
leted, and those
values which
have been set by
potentiometer are
activated.
Dimming (=> see page 2, point 8)
The following approach will prove useful when setting a command
value (example workplace): Place a luxmeter flat on the desk,
then, using the remote control IR-PD4-TRIO-DALI, adjust the light up
or down by pressing the keys max or min until the desired com-
mand value which best suits your requirements has been reached.
Saving of the through adjusted luminance set point
100 h function
to extend the life span – sums up automatically the burning time
of 100 % luminosity at the beginning up to 100 hours – only
then can lights dim
Activate test mode - when locked
Deactivate test mode: press Reset
Resetting when locked
The lighting relay is switched off, i.e. opened and the follow-up
times reset.
Permanent protection against sabotage when locked
This function blocks the unit permanently (all LEDs are flashing).
All functions of the remote control are locked. Proceed to exit this
mode: reset the hardware using DIP switch 3 or switch the supply
voltage as follows:
DA 1/2 ON/OFF when locked (=> see page 2, point 9)
The light will remain switched on/off for as long as movements
are detected in the areas of coverage. Once the last movement
has been detected, the light will remain on for the duration of
the follow-up time as per setting.
The appliance will then return independently to the mode
selected (Fully or Semi-automatic).
Orientation lighting and its follow-up time ON/OFF
Note: During the orientation light phase, the constant light
regulation is also active: if there is sufficient brightness, dimming
occurs < 2V and, if applicable, the lighting is switched off.
Orientation lighting – Adjustment ot the light intensity
The orientation lighting is adjustable in a span from 10 to 30 %
of the nominal light. Standard adjustment is 20 %.
Explanation of the key functions
1000
100
h
100
to
6
5
4
A
3
2
1
B
DIP 1 HA / A
DIP 2 Ini OFF/ON
Lamps at start-up OFF/ON
DIP 3 RESET
5. Position of potentiometer and DIP switch
SM
FC
3
1
2
DIP
123
DIP
321
1 2 3
ON
230V
1sec. 1sec.30 sec. - 60 sec.
OFF
The detector must be in stalled on a solid and
level surface. The circular cover ring must be
removed prior to assembly. To do this, twist the
lens (C) anticlockwise through approximately 5°
and lift off.
Having connected up the wires in accordance with
regulations, secure the detector with 2 screws.
After installation replace the lens and lock (turn
clockwise). Mains to be connected
.
open
close
A circular opening
of diameter 100 mm
must be produced in
the ceiling.
Having connected
up the cables in
accor dance with
regulations, the
detector is inserted
into the opening as
shown and fixed
into position with
the retaining bracket
using screws.
4. Putting into operation of the
remote control (optional)
Remote control
LUXOMAT
®
IR-PD4-TRIO-DALI
1. Check Battery:
open battery compartment by pressing
the plastic springs together and remo-
ving the battery-holder.
Caution:
Settings with remote control supersede
the settings by courtesy of potentio-
meters.
Unlocking device
Dimming of the luminance set
point (only for channel 1 and 2)
Luminance set point for
constant light regulation
Sun button – preselected light value
(Daylight operation)
Follow-up time light
100 h function
Orientation lighting and its
follow-up time ON/OFF
Orientation lighting
follow-up time
Orientation lighting
10 – 30% of nominal light
Saving of the dimmed
luminance set point
SM FC
t < 5 sec.
max
50
Lux
1500
Lux
ON
OFF
Locking device – Exit
programming mode
Permanent protection against
sabotage
LED ashes
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - PD4-M-TRIO-DALI

Installation and Operating Instruction for B.E.G.-Occupancy detectors PD4-Master-TRIO-DALI-SM/-FCA Light sensor 1 | B Light sensor 21 LED red

Seite 2

15. Technical data PD4-M-TRIO-DALI Sensor and power supply in one casePower supply: 230V~ ±10%Power consumption: < 1WAmbient temperature: -25

Kommentare zu diesen Handbüchern

Keine Kommentare